The ROS-2210 combines reverse osmosis control and dual conductivity measurement. It is equipped with a typical process control program for the RO system. It can easily and clearly view the measurement data of the inlet water conductivity and produced water conductivity and the operating status of the RO equipment. Combine PLC and two-way conductivity meter.
The latest full-view LCD screen and image flow control panel make it easier to reflect the status of pumps, valves and pressure detection. The menu parameter settings in the password mode can meet the various indicators of the system automatic operation.
The instrument has been further optimized with many improvements and version upgrades. It is very suitable for the automatic management of the first-stage reverse osmosis water-making equipment. It only needs to add a small amount of electrical components to achieve manual and automatic double compatibility. In a typical system, the complicated problems are simplified.
Main Technical Specification
| Measuring range | source water: 0 ~ 2000us / cm | Water production | 0 ~ 2000us / cm |
| Matched electrode | ABS1.0 platinum black electrode, Cable length 4.5 meters | Qty | 2pcs |
| Power supply | AC220V ±15% 50HZ | Optional | DC24V power supply |
| Power consumption | ≤10W | Accuracy | 1.5% FS |
| Environmental conditions | Temperature: 5~60°C | Humidity | ≤85%RH |
| Output | 3A/250V AC (solenoid valve and pump must be driven by intermediate relay) | Medium temperature | 5~60 °C |
| Conductivity working pressure | 0~0.5 MPa | Measuring distance | no more than 30m |
| Temperature compensation | automatic temperature compensation based on 25 °C | Dimensions | 96*96*130 mm (L *W *D) |
| Display mode | full-view LCD liquid crystal display | Dial opening | 92*92mm |